Description
System
Pro M compact S200 miniature circuit breakers are current-limiting. They have
two different tripping mechanisms: the delayed thermal tripping mechanism for
overload protection and the electromechanic tripping mechanism for short
circuit protection. They are available in different characteristics
(B,C,D,K,Z), configurations (1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to
6 kA at 230/400 V AC), and rated currents (up to 63A). All MCBs in the product
range S200 comply with IEC/EN 60898-1, IEC/EN 60947-2, and UL1077, allowing the
use for residential, commercial, and industrial applications. Bottom-fitting
auxiliary contact can be mounted on S200 to save 50% space.
Technical Details
Standards |
IEC/EN
60898-1 IEC/EN
60947-2 UL
1077 |
Tripping
Characteristic |
C |
Rated
Operational Voltage |
acc.
to IEC 60898-1 400 V AC acc.
to IEC 60898-1 400 V acc.
to IEC 60947-2 440 V AC |
Operational
Voltage |
Maximum
(Incl. Tolerance) 125 V DC Maximum
(Incl. Tolerance) 440 V AC Minimum
12 V AC Minimum
12 V DC |
Rated
Insulation Voltage (Ui) |
acc.
to IEC/EN 60664-1 440 V |
Input
Voltage Type |
AC/DC |
Rated
Short-Circuit Capacity |
(AC)
6 kA (DC)
6 kA (400
V AC) 6 kA (400
V) 6 kA |
Rated
Ultimate Short-Circuit Breaking Capacity (Icu) |
(125
V DC) 10 kA (230
V AC) 20 kA (400
V AC) 10 kA (440
V AC) 10 kA (48
V DC) 20 kA (230
V) 20 kA (400
V) 10 kA |
Ambient
Air Temperature |
Operation
-25 ... +55 °C Storage
-40 ... +70 °C |
Degree
of Protection |
IP20 IP40 Enclosure
with Cover IP40 |
Reference
Ambient Air Temperature |
30
°C |